General Technical Data

Example

here: Installation instructions and structural features

 

Standard cable duct lengths and associated possible access opening positions and sizes

These ducts can be supplied with access openings of either 1.40 x 0.70 m (standard) or 2.10 x 0.70 m. Custom-made access openings available upon request.

  • The small letters designate 1.40 x 0.70 m access openings
  • The capital letters designate 2.10 x 0.70 m access openings  

Clear CD length in m Potential access opening position and size1)
2,50a/A; c/C
3,90a/A; c/C
5,00a/A; b/B, c/C2)
6,10a/A; b/B, c/C2)
7,20e/E; f/F; g/G; h/H; i/I; k/K

1)2.10 x 0.70 m access opening(s) must only be used if the cable duct neck can be installed to a height above ground of at least 0.85 m, which is the minimum height required in order to be able to install the duct neck frame with the conical bottom.

2)Can be custom-supplied upon request.

Access opening position

Access opening

Description
a/AK-Sch
  • Access opening in the centre
  • Prohibited from use where cables are stored on one side only
b/BK-Sch
  • Access opening at the side
  • Prohibited from use where cables are stored on both sides of the duct
c/CK-Sch
  • Offset access opening at the side
  • Prohibited from use where cables are stored on one side only
e/EK-Sch
  • Two centrally-positioned, serial access openings
  • For ducts with a length of l < 6.10 m
  • Prohibited from use where cables are stored on one side only
f/FK-Sch
  • Two centrally-positioned, serial access openings, one of which is offset to the side
  • For ducts with a length of l < 6.10 m
  • Prohibited from use where cables are stored on one side only
g/GK-Sch
  • Two serial access openings, offset to the side
  • For ducts with a length of l < 6.10 m
  • Prohibited from use where cables are stored on both sides of the duct
h/HK-Sch
  • Two side-, serial access openings, one of which is offset to the side
  • For ducts with a length of l < 6.10 m
  • Prohibited from use where cables are stored on both sides of the duct
i/IK-Sch
  • Two centrally-positioned, serial access openings
  • Only suitable for use in ducts with divided ceilings
    (CD L2, l = 7.20 m)
  • Prohibited from use where cables are stored on one side only
k/kK-Sch
  • Two serial access openings, offset to the side
  • Only suitable for use in ducts with divided ceilings
    (CD L2, l = 7.20 m)
  • Prohibited from use where cables are stored on both sides of the duct

 

top of the page